Voltage Drop Calculator (60364-5-52 - IEC:2009)

Full Load current: [A]
Voltage: [V]
No phases:
Power factor: [pu]
Conductor material:
Select cable size: [mm2]
Cable length: [m]
THE RESULT:
Table G.52.1 – Voltage drop
Type of installation Lighting
%
Other uses
%
A – Low voltage installations supplied directly from a public low voltage distribution system 3 5
B – Low voltage installation supplied from private LV supply* 6 8
* As far as possible, it is recommended that voltage drop within the final circuits do not exceed those indicated in installation type A.
When the main wiring systems of the installations are longer than 100 m, these voltage drops may be increased by 0,005 % per meter of wiring system beyond 100 m, without this supplement being greater than 0,5 %.
Voltage drop is determined from the demand by the current-using equipment, applying diversity factors where applicable, or from the values of the design current of the circuits.



Conductor sizing (60364-5-52 -IEC:2009)

- Selection of conductor type and insulation.
- Selection of method of installation.
- Taking account of correction factors for different environmental conditions.
- Determination of cross-sectional areas using tables giving the current carrying capacity.


LOAD INFORMATION
Full Load current: [A]
CABLE SPECIFICATION
Conductor material:
Insulation type:
Number of cores:
INSTALLATION CONDITIONS
Installation reference method:
Ambient temperature: [C]
No. of grouped cables:
Installation type:
Nature of soil:
The Result: